Feature of Epoxy Resin Cast Dry-Type Power Transformer
This series of dry-type transformers are used to directly reduce 35KV electrical grid power supply to 400V distribution power supply for users and omits the stage of 10KV transmission and transformation., which significantly decreases operating costs and engineering construction costs of multi-level substation projects, and have significant social benefits. By optimizing the structure of the high-voltage coil, the distributions of voltage and capacitance between layers are improved, which greatly enhances the impact resistance of products to withstand atmospheric over-voltage and operating over-voltage, as well as improves the electric field distribution and further reduces the partial discharge volume of product.
Technical Requirement of Epoxy Resin Cast Dry-Type Power Transformer
Environment: -25℃~40℃
Altitude(m): 100 meters or less
Insulation Class: F Class
Frequency(Hz): 50
Tap Range: 50-160KVA:±2.5%、±5%; 200-2500KVA:±5%、±2*2.5%
Voltage Regulating Mode: No-load Voltage Regulating
Cooling Type: AN/FN
Technical Parameter of Epoxy Resin Cast Dry-Type Power Transformer
Executive Standard: IEC60076 & National Standard
HV:35/36/37/38.5 LV:0.4/0.415 | |||||
Capacity | Connection Group |
No-Load Loss W |
On-Load Loss W |
No-Load Current % |
Short-Circuit Impedance % |
50 |
Yyn0 Dyn11 |
450 | 1420 | 2.3 | 6 |
100 | 630 | 2090 | 2 | 6 | |
160 | 790 | 2810 | 1.5 | 6 | |
200 | 880 | 3320 | 1.5 | 6 | |
250 | 990 | 3800 | 1.3 | 6 | |
315 | 1170 | 4510 | 1.3 | 6 | |
400 | 1370 | 5410 | 1.1 | 6 | |
500 | 1620 | 6650 | 1.1 | 6 | |
630 | 1860 | 7690 | 1 | 6 | |
800 | 2160 | 9120 | 1 | 6 | |
1000 | 2430 | 10400 | 0.75 | 6 | |
1250 | 2830 | 12700 | 0.75 | 6 | |
1600 | 3240 | 15400 | 0.75 | 6 | |
2000 | 3820 | 18200 | 0.75 | 6 | |
2500 | 4450 | 21800 | 0.75 | 6 |